UL 60079-6

Original price was: $250.00.Current price is: $150.00.

Explosive Atmospheres – Part 6: Equipment Protection by Liquid Immersion 'o'

Published by Publication Date Number of Pages
UL 04/29/2016 0
Category:

Description

UL 60079-6 – Explosive Atmospheres – Part 6: Equipment Protection by Liquid Immersion 'o'

1 Scope
1DV.1 Modification of Clause 1, first paragraph to replace with the following:

1DV.1.1 This standard part of IEC 60079 specifies the requirements for the design, construction, testing and marking of Ex Equipment and Ex Components with type of protection liquid immersion “o” intended for use in explosive gas atmospheres.
Ex Equipment and Ex Components of type of protection liquid immersion “o” are either:

  • Level of Protection “ob” (EPL “Mb” or “Gb”)
  • Level of Protection “oc” (EPL “Gc”)

For Level of Protection “ob”, this standard applies where the rated voltage does not exceed 11 kV r.m.s. a.c. or d.c.
For Level of Protection “oc”, this standard applies where the rated voltage does not exceed 15 kV r.m.s. a.c. or d.c.
NOTE Requirements for higher voltages are under consideration.

1DV.2 Modification of Clause 1, fifth paragraph to replace with the following:
1DV.2.1 This standard supplements and modifies the general requirements of UL 60079-0 IEC 60079-0. Where a requirement of this standard conflicts with a requirement of UL 60079-0 IEC 60079-0, the requirement of this standard takes precedence.

Product Details

Edition:
4
Published:
04/29/2016
Note:
This product is unavailable in Ukraine, Russia, Belarus